Inside MECC-108: Thermal Validation Of A 108kWh Battery Cabinet From -20°C To 50°C

Nov 26, 2026 Leave a message

Why Thermal Validation Decides Whether a 108kWh Cabinet Survives Its First Winter

 

A 108kWh battery cabinet can look perfect on a datasheet and still fail in the field - not because the cells are wrong, but because the temperature around them is. LFP cells charge poorly when cold, age quickly when hot, and lose usable capacity whenever a pack develops a large internal temperature spread. In an off-grid installation, where the battery is the only source of power and no technician is on site, thermal behaviour is not a comfort feature. It is the difference between a system that delivers rated energy for a decade and one that derates, alarms or shuts down in the first extreme season.

 

That is why MECC ran a dedicated thermal management design-verification programme on the MECC108 - a 108kWh lithium iron phosphate battery cabinet built from 314Ah cells. The test asked a simple question: can the cabinet charge and discharge at its full 0.5P rate, without alarm or power derating, when the ambient environment is 25°C, 50°C or -20°C?

 

This article walks through the test platform, the procedure, the measured temperature rise and spread at each set point, and the control logic the BMS and HVAC system executed to keep every cell inside its safe window.

 

 

Figure 1 - MECC108 108kWh battery cabinet on the thermal test platform. The white enclosure, upper ventilation module and fan grilles are visible, with the green status indicator lit and sensor leads connected for data acquisition.

news-543-928

 

The System Under Test: 108 cells, Two Modules, One 57.6V Pack Architecture

 

The MECC108 test article was a production-intent 108kWh cabinet, assembled from the same building blocks used in MECC's modular battery product line:

 

Cell: 3.2V / 314Ah LFP prismatic cell, 1,004.8Wh nominal, charge cutoff 3.65V, discharge cutoff 2.5V.

 

Module: 1P9S configuration, 28.8V nominal, 314Ah / 9.04kWh per module; two modules per pack.

 

Pack: 1P18S configuration, 57.6V nominal, 314Ah / 18.09kWh per pack.

 

Cabinet cooling method: forced air cooling, with fan control and heating managed by the battery management system.

Eighteen cells in series make one 57.6V pack, and six such packs in series make the 345.6V / 108kWh system. Across those 108 cells, the BMS monitors temperature at multiple sense points on every battery module (labelled BMU1 through BMU6 in the test curves below). The test measured not just the average cell temperature but the spread between the hottest and coldest sensor - the figure that determines whether a pack will be limited by its weakest cell.

 

 

Test Platform and Instrumentation

 

Two pieces of equipment defined the test boundaries:

 

A programmable power distribution cabinet rated for AC 380V with a bidirectional current range of -200A to +200A, used to drive the 0.5P constant-power charge and discharge cycles.

 

A walk-in environmental chamber with a temperature range of -20°C to 50°C and a humidity range of 0–98% RH, used to soak the cabinet at each ambient set point before and during cycling.

 

During the test the BMS logged power (P), elapsed time (t), total pack voltage (U), individual cell voltage (u), cell temperature (T), charge and discharge energy (Ec / Ed), and charge and discharge capacity (Qc / Qd) - all to two decimal places. That data stream is what produced the temperature curves reproduced later in this article.

 

 

Test Procedure: 0.5P Cycling at Three Ambient Set Points

 

All three scenarios followed the same logic: discharge to the cell cutoff voltage, soak the battery at the target ambient temperature, then run repeated 0.5P constant-power charge and discharge steps with a 10-minute rest after each. The 25°C case additionally repeated the charge/discharge pair twice to establish a room-temperature baseline.

 

 

Figure 2 - English translation of the test flowchart: platform setup, 0.5P discharge, environmental adaptation at 25°C / 50°C / -20°C, 0.5P charge, 0.5P discharge, data logging and teardown.

Step

25°C Ambient

50°C Ambient

-20°C Ambient

1. Platform setup

HV harness, comms harness, fan ducts connected

Same

Same

2. Initial discharge

0.5P constant power to cell cutoff voltage

Same

Same

3. Environmental adaptation

Chamber 25°C; cells equilibrated to 25±1°C (fan-assisted)

Chamber 50°C; soak 16 h or cells to 50±1°C

Chamber -20°C; soak 24 h or cells to -20±1°C

4. Active thermal mode

Fan (ventilation) mode

Cooling mode (avg cell temp >30°C)

Heating mode (avg cell temp <12°C); brief low-temp power limit

5. Charge

0.5P to cutoff, then 10-min rest

Same

Same

6. Discharge

0.5P to cutoff, then 10-min rest

Same

Same

7. Repeat pair

One extra charge/discharge pair (baseline run)

-

-

8. Data logging

P, t, U, cell voltage, T, Ec, Qc

Same

Same

9. Teardown

Platform removed, harnesses organised

Same

Same

 

 

25°C baseline. After platform setup and an initial 0.5P discharge, the chamber was set to 25°C and the cells were equilibrated to 25±1°C, with air cooling enabled to speed up stabilisation. The battery then completed a 0.5P charge, a 0.5P discharge, a second 0.5P charge and a second 0.5P discharge - each followed by a 10-minute rest - before data reduction and teardown.

 

50°C hot case. The same initial discharge was followed by a 16-hour soak at 50°C (or until the average cell temperature stabilised at 50±1°C). With the cells hot, the system ran one 0.5P charge and one 0.5P discharge, each with a 10-minute rest. This scenario exercised the cooling logic: above 30°C average cell temperature, the control strategy switched the HVAC into cooling mode.

 

-20°C cold case. After the initial discharge, the cabinet was soaked for 24 hours at -20°C (or until the average cell temperature reached -20±1°C). It then completed one 0.5P charge and one 0.5P discharge with rests. Below 12°C average cell temperature, the control strategy switched to heating mode - the scenario that determines whether a BESS can operate through a northern-hemisphere winter.

 

The criterion for all three was exploratory rather than pass/fail - the report classifies them as design-verification "no judgement" runs - but the acceptance intent was explicit: no high-temperature alarm, no low-temperature alarm, and no unexplained power derating once the thermal strategy had brought the cells into range.

 

 

Results at 25°C: Stable Room-Temperature Operation

 

During charge/discharge at 25°C, the cell average temperature stayed between 23°C and 28°C. The control strategy triggered fan mode, and temperature rise and spread both remained inside the design target. No alarm and no power limiting occurred.

 

 

Figure 3 - Charge/discharge BMS alarms and average temperature curve at 25°C. The blue trace is the pack average temperature; red vertical markers indicate HVAC fault start and end events logged during the run.

news-1118-754

 

 

 

Figure 4 - Individual BMS cell temperature curves at 25°C, one trace per sensor across six battery management units. The spread between the hottest and coldest cell stays narrow throughout the two charge/discharge cycles.

news-1222-818

 

 

The measured numbers at 25°C were a maximum of 32.3°C, a minimum of 24.4°C, a maximum rise of 7.1°C, an average rise of 5.79°C, a maximum sensor-to-sensor spread of 5°C and an average spread of 4.06°C. The run establishes the baseline: an air-cooled cabinet with well-matched cells holding a 4–5°C spread and a single-digit rise above ambient. On both counts the MECC108 behaved as designed.

 

 

Results at 50°C: Cooling Holds the Pack Inside Its Window

 

At the 50°C set point, the pack was first characterised during the hot soak and then during active 0.5P cycling. The numbers tell the story of a cooling system that kept up with the load:

 

During soak: maximum cell temperature 34.3°C, minimum 23.2°C, maximum rise 9.1°C, average rise 7.06°C, maximum spread 6°C, average spread 3.66°C.

 

During charge/discharge: maximum 38.9°C, minimum 25.2°C, maximum rise 10.6°C, average rise 9.55°C, maximum spread 5.1°C, average spread 3.55°C.

 

The most revealing figure is the average spread during cycling: 3.55°C. Even while pushing 0.5P in a 50°C chamber, the 108 cells stayed within roughly three and a half degrees of one another - a sign that both the airflow design and the cell matching are doing their job.

 

 

Figure 5 - BMS average temperature and alarm markers during the 50°C hot soak. The staircase-like trace reflects the HVAC controller cycling to hold the battery at the target temperature.

news-1260-824

 

 

 

Figure 6 - Per-cell temperature curves during the 50°C soak. The band of traces converges as the cabinet equalises, with the red RMS trace tracking the overall level.

news-1266-828

 

 

 

Figure 7 - Average temperature and alarm markers during 0.5P charge/discharge at 50°C. Average cell temperature exceeded 30°C, triggering cooling mode; no high-temperature alarm or derating followed.

news-1104-684

 

 

 

Figure 8 - Individual cell temperature curves during 50°C cycling. The traces stay bundled in a narrow band with no runaway hot spot, even at the peak of the discharge steps.

news-1250-792

 

 

The MECC conclusion is direct: once average cell temperature rose above 30°C, the control strategy triggered cooling mode, cell temperature was stabilised inside the target range, and neither a high-temperature alarm nor power limiting occurred. The hot-case thermal-management requirement was met.

 

 

Results at -20°C: Heating Brings the Pack Back from a Cold Start

 

The cold case is where most batteries reveal their weakness. At -20°C the MECC108 was soaked for a full 24 hours before cycling - long enough for every cell to reach the ambient temperature and for any weakness in the heating strategy to show up.

 

During soak: maximum cell temperature 30.5°C, minimum 3.6°C, maximum rise 25.7°C, average rise 21.23°C, maximum spread 8.9°C, average spread 6.2°C.

 

During charge/discharge: maximum 33.1°C, minimum 5.8°C, maximum rise 22°C, average rise 20.25°C, maximum spread 11°C, average spread 7.84°C.

 

A 20°C-plus average rise is exactly what a heating system should produce in this environment: the cells started far below their charging window and were brought up into it. The larger spread (up to 11°C) during the cold test is expected - heating elements warm some sensor points faster than others - and stayed inside the design limits of the strategy.

 

 

Figure 9 - Average temperature and alarm markers during the -20°C cold soak. The steady climb from single digits toward the target range shows the heating system working before any charge current is applied.

news-1130-744

 

 

 

Figure 10 - Per-cell curves during the -20°C soak. Initial temperature variation between sensor points narrows as the heating cycle progresses.

news-1232-836

 

 

 

Figure 11 - Average temperature and alarm markers during 0.5P charge/discharge at -20°C. Low-temperature power limiting protects the cells early in the test; once heating lifts the pack above 12°C, normal operation resumes with no low-temperature alarm.

news-1136-742

 

 

 

Figure 12 - Individual cell curves during -20°C cycling. All sensor points rise together into the operating window, with no cell left behind.

news-1260-850

 

 

In the report's own conclusion: with average cell temperature below 12°C, the system triggered heating mode. At the start of the test, low cell temperature activated low-temperature power limiting as a protection measure; the heater then ran continuously, cell temperature climbed progressively into the target range, and no low-temperature alarm was triggered. The cold-weather heating strategy was validated as effective.

 

 

Reading the Curves: What the Vertical Markers Mean

 

In every average-temperature chart above, the red and blue vertical lines are not measurement noise - they are controller events. A red line marks the start of an HVAC fault condition and a blue line marks its end, recorded by the BMS during the test. Their repeated appearance in pairs shows how the thermal controller detected a fault, responded, recovered and then continued to regulate temperature without interrupting the charge/discharge sequence. For an engineer reviewing the data, these markers are the clearest evidence that the cabinet did not simply survive the temperature extremes - it actively managed them.

 

 

From Test Data to Field Value

 

Thermal validation at three set points is not an academic exercise. It maps directly onto the conditions a real battery cabinet will face:

 

Hot climates and desert installations: the 50°C result shows that forced-air cooling can hold a 108kWh pack below 39°C with a 3.55°C average spread, so the system keeps delivering power instead of derating on a hot afternoon.

 

Cold climates and northern winters: the -20°C result shows that the heating strategy lifts cells from single digits into their operating window and that temporary power limiting protects the pack until it gets there - the behaviour that prevents cold-weather charging damage.

 

Daily cycling: the 25°C baseline confirms low rise and tight cell matching under normal operation, which is what protects cycle life over thousands of charge/discharge events.

 

Off-grid reliability: no alarm and no sustained derating appeared in any of the three scenarios. For a remote site with no technician on call, that is the outcome that matters.

 

 

Conclusion: A Cabinet Validated Across Its Real Operating Envelope

 

The MECC-108 thermal test covered the full temperature envelope a 108kWh outdoor cabinet is likely to see: a 25°C baseline, a 50°C high-temperature challenge and a -20°C cold-start challenge. Across all three, MECC's 314Ah LFP cells - arranged as 1P9S modules, 1P18S packs and a 345.6V system - stayed under control:

 

At 25°C, average temperature held between 23°C and 28°C with fan mode active; no alarm or derating.

At 50°C, cooling mode activated above 30°C, peak cell temperature was limited to 38.9°C and average spread during cycling was just 3.55°C; no high-temperature alarm.

At -20°C, heating mode brought the pack from below 12°C into range; brief low-temperature power limiting protected the cells, and no low-temperature alarm was triggered.

 

For specifiers, EPC contractors and off-grid site owners, the message is straightforward: this is a cabinet whose thermal claims are backed by measured curves, not just a nameplate. Looking for a 108kWh battery system with validation data you can actually read? Contact MECC for the full MECC108 specification pack.

 

 

 

 

 
news-1460-1460

MECC 50KW 108KWH BESS Battery Energy Storage System

 

The MECC 50kw 108kWh Battery Energy Storage Cabinet is a high-capacity energy storage solution designed for industrial and commercial applications. Featuring 345.6V, 314Ah lithium iron phosphate (LiFePO4) battery, it ensures long-lasting, safe, and efficient energy storage.

High-efficiency 50kW/108kWh Industrial and Commercial Energy Storage System (C&I ESS). Features LiFePO4 battery, peak shaving, and smart EMS. Reduce operational costs and ensure power backup. Inquire for custom BESS solutions.

Designed with a compact footprint of less than 1.2 square meters, this 108kWh cabinet features a pre-integrated all-in-one design, reducing on-site installation time by 40% compared to modular rack systems.

 

 

 

 

 

MECC | 108kWh Lithium Battery Cabinets, Packs & Energy Storage Systems

Send Inquiry

whatsapp

Phone

E-mail

Inquiry